Plus-X 600


Versatile I/O

The Plus-X 600 is designed to be a versatile I/O solution, suitable for a wide range of applications. Its 1RU form factor allows maximum functionality in minimal space, with a cost effective combination of channels.

Easy Installation

Thanks to IP connectivity between the Plus-X 600 and the ARC Plus, installation is straightforward. Sample voltages connect directly to the Plus-X 600 using the included Phoenix-type connectors. There is no need for external breakout panels.

Affordable Expansion Options

The Plus-X 600 is part of the Plus-X family of ARC Plus Ethernet I/O devices. Expanding an ARC Plus system is easy and affordable. IP connectivity allows installation of additional units virtually anywhere, and the 256 channel capacity of the ARC Plus leaves plenty of room for future expansion.

Dimensions:

1.75" (4.45cm) H
19" (48.26cm) W
12" (30.48cm) D

Operating Temperature:

0° to 40° C

Power Requirements:

100 to 240VAC, 47–63Hz, 1A;
Power entry module with standard, grounded power cord supplied;
1A fuse protection

Connectivity:

Ethernet connection to ARC Plus

Channel Capacity:

16 status, 8 metering, 6 command channels

Metering Input Range:

> 99.75% accuracy, full scale

Status Input Range:

> 0 to +28VDC or switch closure

Output Types:

C, NO, NC relay outputs;
momentary or latching;
5A, 240VAC


Plus-X IIU Plus-X ICRU Plus-X 300 Plus-X 600 Plus-X Dual IP-8 Adapter
Number of metering inputs 16 0 up to 8** 8 8 or 16***
Number of status inputs up to 32* 0 up to 8** 16 8 or 16***
Number of Form-C relays 0 8 pairs 8 6 pairs 8 or 16 pairs***

* 16 dedicated status inputs, and 16 metering or status inputs

** 8 inputs, selectable as metering or status

*** The Plus-X Dual IP-8 Adapter uses the metering, status and relay channels from up to two existing ARC-16 IP-8s.

Line Voltage Sensor

Part #: LVS

Monitor AC Power Circuits

Each LVS monitors a single phase AC power circuit and provides a low-voltage DC output sample that tracks linearly with the AC input voltage. Additional LVS units can be added to monitor multi-phase AC power systems.

Learn More

AC Current Sensor

Part #: 910-093-001

Combined Transformer and Signal Conditioner 

The AC Current Sensor combines a transformer and a signal conditioner into one package. The AC Current Sensor has a selectable input range and an industry standard 0-5VDC output. The AC Current Sensor is designed for application on "linear" or sinusoidal AC loads and is housed in a solid-core case.

Learn More

Magnetic Door Contact

Part #: DOOR CONTACT

Magnetic surface mount switch for windows and doors to indicate closed or open position. Requires 2-conductor cable

Tower Light Monitor

Part #: TLM

Monitor Steady or Flashing Beacon Lamps

The TLM is a universal lamp alarm relay designed to sense the failure of flashing or steady incandescent beacon lamps or steady side lights. The toroidal current sensor provides islolation and allows monitoring of more than one line at a time. The TLM energizes when one or more lamps fail. It will monitor the operation of up to four side lights or four beacon lamps.

Learn More

Tower Light Monitor - LED

Part #: TLM-LED

Monitor Steady or Flashing LED Beacon Lamps

The TLM-LED is a universal lamp alarm relay designed to sense the failure of flashing or steady LED beacon lamps or obstruction lamps. The TLM-LED energizes when one or more lamps fail. It will monitor the operation of one to eight beacon or obstruction lamps. All monitored lamps must be the same wattage and voltage. When properly integrated with ARC Plus or ARC Solo systems, it provides the remote lamp monitoring protection required by the FAA-AC No: 150/5345-43E.

Operation

When a lamp fails, the TLM-LED senses a decrease in current flow. After a 10s trip delay, the onboard LED glows and the two alarm outputs energize. The outputs and the LED are reset when the failed lamps are replaced and the unit is recalibrated. Removing the input voltage de-energizes the output and the LED‘s. 

Learn More

Ordering information

Part #Product
PLUS-X 600Plus-X 600 Input/Output UnitRequest quote

Key Features

  • 16 status inputs
  • 8 meter inputs
  • 6 raise/lower relay pairs, usable as 12 individual relays
  • Ethernet link to ARC Plus